Ecuador (ARCONEL-001/24 Código de Conexión) — ride-through requirements
The LVRT, FRT envelopes a grid-scale battery must meet under Ecuador (ARCONEL-001/24 Código de Conexión) (Ecuador), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.25s → 0 pu; 0.251s → 0.25 pu; 0.56s → 0.4 pu; 0.88s → 0.55 pu; 1.19s → 0.7 pu; 1.5s → 0.85 pu; 3600s → 0.9 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 63 Hz; 90s → 63 Hz; 90.001s → 62 Hz; 1800s → 62 Hz; 1800s → 61 Hz | Low: 0.1s → 57.5 Hz; 90s → 57.5 Hz; 90.001s → 58 Hz; 1800s → 58 Hz; 1800s → 59 Hz | verified |
Where these values come from
- LVRT Regulación Nro. ARCONEL-001/24 «Código de Conexión del Sistema Eléctrico Ecuatoriano» (expedida por Resolución ARCONEL-003/2024, Sesión de Directorio de 04 de septiembre de 2024), numeral 22.2 lit. a) y Gráfico 8; banda de Tabla 8 (numeral 22.1 lit. a); categorías en Tabla 1.
- FRT Regulación Nro. ARCONEL-001/24, ARTÍCULO 19 numeral 19.1 lit. a), Tabla 3; made applicable to category D by the opening paragraph of ARTÍCULO 22.
Last checked against the source document on .
Other grid codes in South America
- Argentina (CAMMESA PT-4 Anexo I, Fig. Ai.1 Argentina · HVRT, LVRT
- Argentina (CAMMESA PT-4) Argentina · FRT
- Brazil (PRODIST / ONS) Brazil · FRT, HVRT, LVRT
- Chile (NTSyCS) Chile · HVRT, LVRT
- Colombia (CREG 060/2019, red de 500 kV) Colombia · HVRT
- Colombia (CREG 060/2019) Colombia · HVRT, LVRT
- Panama (Código de Redes Fotovoltaico 2017) Panama · FRT, HVRT, LVRT
- Peru (COES PR-20, Anexo 1 Cap. 4 Peru · FRT, LVRT