Peru (COES PR-20, Anexo 1 Cap. 4 — ride-through requirements
The LVRT, FRT envelopes a grid-scale battery must meet under Peru (COES PR-20, Anexo 1 Cap. 4 (Peru), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.15s → 0 pu; 0.4s → 0.1 pu; 0.65s → 0.2 pu; 1.43s → 0.42 pu; 2.22s → 0.63 pu; 3s → 0.85 pu; 62s → 0.88 pu; 121s → 0.92 pu; 180s → 0.95 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 62 Hz; 30s → 62 Hz; 30.001s → 61.6 Hz; 1800s → 61.6 Hz; 1800s → 60.6 Hz | Low: 0.1s → 57 Hz; 10s → 57 Hz; 10.001s → 57.8 Hz; 30s → 57.8 Hz; 30.001s → 58.4 Hz; 1800s → 58.4 Hz; 1800s → 59.4 Hz | verified |
Where these values come from
- LVRT Procedimiento Técnico del COES N° 20 (PR-20), Anexo 1, Capítulo 4, numeral 4.4.3 (viñeta 'Comportamiento Transitorio') y Figura 4.4 'Curva tensión-tiempo del sistema de protección de tensión por fase'; band from 4.4.6; extended to storage by 4.5.1. Aprobado por Res. Consejo Directivo Osinergmin N° 173-2024-OS/CD.
- FRT PR-20, Anexo 1, Capítulo 4, numeral 4.4.5 'Tolerancia ante variaciones de la frecuencia', Tabla 4.5 'Tolerancias de Frecuencia de la CGNC'. Res. Consejo Directivo Osinergmin N° 173-2024-OS/CD.
Last checked against the source document on .
Other grid codes in South America
- Argentina (CAMMESA PT-4 Anexo I, Fig. Ai.1 Argentina · HVRT, LVRT
- Argentina (CAMMESA PT-4) Argentina · FRT
- Brazil (PRODIST / ONS) Brazil · FRT, HVRT, LVRT
- Chile (NTSyCS) Chile · HVRT, LVRT
- Colombia (CREG 060/2019, red de 500 kV) Colombia · HVRT
- Colombia (CREG 060/2019) Colombia · HVRT, LVRT
- Ecuador (ARCONEL-001/24 Código de Conexión) Ecuador · FRT, LVRT
- Panama (Código de Redes Fotovoltaico 2017) Panama · FRT, HVRT, LVRT