NERC PRC-024-4 (ERCOT) — ride-through requirements
The FRT envelope a grid-scale battery must meet under NERC PRC-024-4 (ERCOT) (US), digitized breakpoint by breakpoint and checked against the clause it came from. This is a protection-setting no-trip boundary, not a ride-through performance duty.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| frequency ride-through (FRT) | no-trip | High: 0.1s → 61.8 Hz; 30s → 61.8 Hz; 30.001s → 61.6 Hz; 540s → 61.6 Hz; 540.001s → 60.6 Hz | Low: 0.1s → 57.5 Hz; 2s → 57.5 Hz; 2.001s → 58 Hz; 30s → 58 Hz; 30.001s → 58.4 Hz; 540s → 58.4 Hz; 540.001s → 59.4 Hz | verified |
Where these values come from
- FRT NERC PRC-024-4, Attachment 1, Table 4 'Frequency Boundary Data Points – ERCOT Interconnection' and Figure 4 (p.15); identical to PRC-024-3 Table 4.
Last checked against the source document on .
Other grid codes in North America
- California Rule 21 US · FRT, HVRT, LVRT
- Canada (Alberta AESO) Canada · FRT, HVRT, LVRT
- ERCOT (NOG 2.6.2.1) US · FRT
- ERCOT (NOG 2.9.1.2 legacy) US · HVRT, LVRT
- ERCOT (NOG 2.9.1) US · HVRT, LVRT
- IEEE 1547-2018 Cat III US · FRT, HVRT, LVRT
- IEEE 2800-2022 US · FRT, HVRT, LVRT
- Mexico (Codigo de Red) Mexico · FRT, HVRT, LVRT
- NERC PRC-024-4 (no-trip) US · HVRT, LVRT
- NERC PRC-024-4 (Western) US · FRT
- NERC PRC-029-1 (IBR) US · FRT, HVRT, LVRT
- NERC PRC-029-1 (Table 1: AC-connected wind IBR /…) US · LVRT