California Rule 21 — ride-through requirements
The LVRT, HVRT, FRT envelopes a grid-scale battery must meet under California Rule 21 (US), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 1s → 0 pu; 1.001s → 0.5 pu; 10s → 0.5 pu; 10.001s → 0.7 pu; 20s → 0.7 pu; 20.001s → 0.88 pu | verified |
| high-voltage ride-through (HVRT) | ride-through | 0.001s → 1.2 pu; 12s → 1.2 pu; 12.001s → 1.1 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 61.8 Hz; 299s → 61.8 Hz; 299.001s → 61.2 Hz | Low: 0.1s → 57 Hz; 299s → 57 Hz; 299.001s → 58.8 Hz | verified |
Where these values come from
- LVRT PG&E Electric Rule 21, Sheet 193, Table Hh-1b 'Smart Inverter Voltage Ride-through Settings' (V>1.20 cease to energize; 1.10<V<=1.20 momentary cessation 12 s; 0.88<=V<=1.10 continuous; 0.70<=V<0.88 mandatory 20 s; 0.50<=V<0.70 mandatory 10 s; V<0.50 momentary cessation 1 s) and Table Hh-1a shall-trip settings (UV1 0.88 / 21.0 s; UV2 0.50 / 2.0 s), Advice 7692-E effective August 29, 2025, Corroborated by the legacy SDG&E Rule 21 Sheet 122 Table Hh-1 (Advice 2860-E, effective July 5, 2016): LV3 V<50% ride-through until 1 sec; LV2 50-70% until 10 sec; LV1 70-88% until 20 sec; NN 88-110% indefinite.
- HVRT PG&E Electric Rule 21, Sheet 193, Table Hh-1b: '1.10 < V <= 1.20 | Momentary Cessation | 12 | 0.083' and 'V > 1.20 | Cease to Energize | NA | 0.16'; Table Hh-1a OV2 1.20 / 0.16 s, OV1 1.10 / 13.0 s. Advice 7692-E effective August 29, 2025, Corroborated by legacy SDG&E Rule 21 Sheet 122 Table Hh-1, HV1 110<V<120, 'Ride-Through Until 12 sec', Momentary Cessation, Maximum Trip Time 13 sec.
- FRT PG&E Electric Rule 21, Sheet 196, Table Hh-2b 'Frequency Ride-Through Settings Table' (f>62.0 no RT; 61.2<f<=61.8 Mandatory Operation 299 s; 58.8<=f<=61.2 Continuous Infinite; 57.0<=f<58.8 Mandatory Operation 299 s; F<57.0 no RT), section Hh 'Smart Inverter Generating Facility Design and Operating Requirements for UL1741SB Inverters', Advice 7692-E effective August 29, 2025, Superseded values from SDG&E Rule 21 Sheet 124 Table Hh-2 (Advice 2860-E, effective July 5, 2016): f>62 no ride-through 0.16 s trip; 60.5<f<62 mandatory 299 s; 58.5<f<60.5 continuous; 57.0<f<58.5 mandatory 299 s; f<57.0 no ride-through 0.16 s trip. Cross-checked against IEEE 1547-2018 Table 18 shall-trip defaults (OF2 62.0/0.16 s, OF1 61.2/300 s, UF1 58.5/300 s, UF2 56.5/0.16 s) as reproduced in NERC Reliability Guideline 'BPS Reliability Perspectives on the Adoption of IEEE 1547-2018', March 2023, Table 1.3.
Last checked against the source document on .
Other grid codes in North America
- Canada (Alberta AESO) Canada · FRT, HVRT, LVRT
- ERCOT (NOG 2.6.2.1) US · FRT
- ERCOT (NOG 2.9.1.2 legacy) US · HVRT, LVRT
- ERCOT (NOG 2.9.1) US · HVRT, LVRT
- IEEE 1547-2018 Cat III US · FRT, HVRT, LVRT
- IEEE 2800-2022 US · FRT, HVRT, LVRT
- Mexico (Codigo de Red) Mexico · FRT, HVRT, LVRT
- NERC PRC-024-4 (ERCOT) US · FRT
- NERC PRC-024-4 (no-trip) US · HVRT, LVRT
- NERC PRC-024-4 (Western) US · FRT
- NERC PRC-029-1 (IBR) US · FRT, HVRT, LVRT
- NERC PRC-029-1 (Table 1: AC-connected wind IBR /…) US · LVRT