ERCOT (NOG 2.9.1) — ride-through requirements
The LVRT, HVRT envelopes a grid-scale battery must meet under ERCOT (NOG 2.9.1) (US), digitized breakpoint by breakpoint and checked against the clause it came from.
Applies to: transmission connections — Transmission-connected IBRs: PVGRs and ESR IBRs (ERCOT).
Part of: the grid-code ride-through chart — compare this against 65 other standards in 44 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source. Binds resources whose SGIA was executed on or after 1 Aug 2024.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries. These are the boundaries, not the behaviour: what holding one demands of the converter — reactive current injection, thermal stress, protection timing — is stepped through in the LVRT / HVRT ride-through visual.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.32s → 0 pu; 0.321s → 0.095625 pu; ↗ 0.594444s → 0.25 pu; 1.2s → 0.25 pu; 1.201s → 0.5 pu; 3s → 0.5 pu; 3.001s → 0.7 pu; 6s → 0.7 pu; 6.001s → 0.9 pu | verified |
| high-voltage ride-through (HVRT) | ride-through | 0.001s → 1.2 pu; 1s → 1.2 pu; 1.001s → 1.1 pu | verified |
Where these values come from
- LVRTERCOT Nodal Operating Guides, Section 2.9.1.1 'Preferred Voltage Ride-Through Requirements for Transmission-Connected Inverter-Based Resources (IBRs)', paragraph (1), Table B: Applicable to PhotoVoltaic Generation Resources (PVGRs) and ESR IBRs, plus the following paragraph defining the sub-0.25 pu straight-line function ('0.15 seconds at zero voltage and 1.75 seconds at 0.9 p.u. voltage'). Source: February 1, 2026 ERCOT Nodal Operating Guide PDF (body dated DECEMBER 5, 2025), sheet pp. 52-54. The code defines a linear recovery ramp; the vertices are read from the clause and the chart draws the segment between them.
- HVRTERCOT Nodal Operating Guides Section 2.9.1(1)(a)/(b) (applicability by SGIA date, no MW threshold); Section 2.9.1.1(1) Tables A and B high-voltage rows (1.10<V<=1.20 -> 1.0 s; V>1.20 may ride-through or trip); Section 2.9.1.2(1) Table A (1.175<V<=1.2 -> 0.2 s; 1.15<V<=1.175 -> 0.5 s; 1.10<V<=1.15 -> 1.0 s). sheets pp. 50-55.
Read it yourself: ERCOT Nodal Operating Guides (PDF) ↗
Any event not in the table above is not plotted for this code. Where an absence is itself the finding — a code that defines no high-voltage envelope, or one whose curves circulate under another country's name — it is recorded in the grid codes with no ride-through curve.
Last checked against the source document on .
How US compares
Each event this code defines, put side by side with every other code that defines it:
- Low-voltage ride-through (LVRT) across 52 codesWhere ERCOT (NOG 2.9.1) sits against every other published LVRT envelope.
- High-voltage ride-through (HVRT) across 33 codesWhere ERCOT (NOG 2.9.1) sits against every other published HVRT envelope.
Other grid codes in North America
- California Rule 21US · FRT, HVRT, LVRT
- Canada (Alberta AESO)Canada · FRT, HVRT, LVRT
- ERCOT (NOG 2.6.2.1)US · FRT
- ERCOT (NOG 2.9.1.2 legacy)US · HVRT, LVRT
- IEEE 1547-2018 Cat IIIUS · FRT, HVRT, LVRT
- IEEE 2800-2022US · FRT, HVRT, LVRT
- Mexico (Codigo de Red)Mexico · FRT, HVRT, LVRT
- NERC PRC-024-4 (ERCOT)US · FRT
- NERC PRC-024-4 (no-trip)US · HVRT, LVRT
- NERC PRC-024-4 (Western)US · FRT
- NERC PRC-029-1 (IBR)US · FRT, HVRT, LVRT
- NERC PRC-029-1 (Table 1: AC-connected wind IBR /…)US · LVRT