Canada (Alberta AESO) — ride-through requirements
The LVRT, HVRT, FRT envelopes a grid-scale battery must meet under Canada (Alberta AESO) (Canada), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.15s → 0 pu; 0.151s → 0.45 pu; 0.3s → 0.45 pu; 0.301s → 0.65 pu; 2s → 0.65 pu; 2.001s → 0.75 pu; 3s → 0.75 pu; 3.001s → 0.9 pu | verified |
| high-voltage ride-through (HVRT) | ride-through | 0.001s → 1.2 pu; 0.2s → 1.2 pu; 0.201s → 1.175 pu; 0.5s → 1.175 pu; 0.501s → 1.15 pu; 1s → 1.15 pu; 1.001s → 1.1 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 61.7 Hz; 30s → 61.7 Hz; 30.001s → 61.6 Hz; 180s → 61.6 Hz; 180.001s → 60.6 Hz | Low: 0.1s → 57 Hz; 0.75s → 57 Hz; 0.751s → 57.3 Hz; 7.5s → 57.3 Hz; 7.501s → 57.8 Hz; 30s → 57.8 Hz; 30.001s → 58.4 Hz; 180s → 58.4 Hz; 180.001s → 59.4 Hz | verified |
Where these values come from
- LVRT AESO ISO Rules Section 503.5 Voltage Ride-Through, Appendix 1 'Voltage Ride-Through Requirements', Low Voltage Ride-Through Duration table: '< 0.45 / 4 to 9 cycles', '< 0.65 / 0.30 seconds', '< 0.75 / 2.00 seconds', '< 0.90 / 3.00 seconds', '>= 0.90 / Continuous operation'; plus subsection 2(2)(c). Effective 2024-04-01.
- HVRT AESO ISO Rules Section 503.5, Appendix 1, High Voltage Ride-Through Duration table: '>= 1.200 / Instantaneous trip', '>= 1.175 / 0.20 seconds', '>= 1.15 / 0.50 seconds', '>= 1.10 / 1.00 seconds', '< 1.10 / Continuous operation'. Also subsection 2(2)(a): continuous operation between 0.90 and 1.10 pu. Effective 2024-04-01.
- FRT AESO ISO Rules Section 503.6, Appendix 1 'Trip Settings for Off-Nominal Frequency Protective Relays': High - '>=61.7 Instantaneous trip', '>=61.6 / 30', '>=60.6 / 180', '<60.6 Continuous operation'; Low - '<=57.0 Instantaneous trip', '<=57.3 / 0.75', '<=57.8 / 7.5', '<=58.4 / 30', '<=59.4 / 180', '>59.4 Continuous operation'. Contrast IESO Market Rules Appendix 4.2 Issue 16.0 category 1 'Off-Nominal Frequency Operation'.
Last checked against the source document on .
Other grid codes in North America
- California Rule 21 US · FRT, HVRT, LVRT
- ERCOT (NOG 2.6.2.1) US · FRT
- ERCOT (NOG 2.9.1.2 legacy) US · HVRT, LVRT
- ERCOT (NOG 2.9.1) US · HVRT, LVRT
- IEEE 1547-2018 Cat III US · FRT, HVRT, LVRT
- IEEE 2800-2022 US · FRT, HVRT, LVRT
- Mexico (Codigo de Red) Mexico · FRT, HVRT, LVRT
- NERC PRC-024-4 (ERCOT) US · FRT
- NERC PRC-024-4 (no-trip) US · HVRT, LVRT
- NERC PRC-024-4 (Western) US · FRT
- NERC PRC-029-1 (IBR) US · FRT, HVRT, LVRT
- NERC PRC-029-1 (Table 1: AC-connected wind IBR /…) US · LVRT