NERC PRC-029-1 (IBR) — ride-through requirements
The LVRT, HVRT, FRT envelopes a grid-scale battery must meet under NERC PRC-029-1 (IBR) (US), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.32s → 0 pu; 0.321s → 0.25 pu; 1.2s → 0.25 pu; 1.201s → 0.5 pu; 3s → 0.5 pu; 3.001s → 0.7 pu; 6s → 0.7 pu; 6.001s → 0.9 pu | verified |
| high-voltage ride-through (HVRT) | ride-through | 0.001s → 1.2 pu; 1s → 1.2 pu; 1.001s → 1.1 pu; 1800s → 1.1 pu; 1800s → 1.05 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 61.8 Hz; 299s → 61.8 Hz; 299.001s → 61.2 Hz | Low: 0.1s → 57 Hz; 299s → 57 Hz; 299.001s → 58.8 Hz | verified |
Where these values come from
- LVRT NERC PRC-029-1, Attachment 1 'Voltage Ride-Through Criteria', Table 2 'Voltage Ride-through Requirements for All Other IBR' (p.12), with Boundary Details bullets 2(b) (PV+BESS → Table 2), 7 and 11 (p.13).
- HVRT NERC PRC-029-1, Attachment 1, Table 2 'Voltage Ride-through Requirements for All Other IBR' (p.12), rows '>1.20 N/A', '>1.10 Mandatory Operation Region 1.0', '>1.05 Continuous Operation Region 1800'.
- FRT NERC PRC-029-1, Attachment 2 'Frequency Ride-Through Criteria', Table 3 'Frequency Ride-through Capability Requirements' and Figure 1 'PRC-029 Frequency Ride-through Requirements' (p.14); Requirement R3 caps applicability at RoCoF ≤ 5 Hz/s.
Last checked against the source document on .
Other grid codes in North America
- California Rule 21 US · FRT, HVRT, LVRT
- Canada (Alberta AESO) Canada · FRT, HVRT, LVRT
- ERCOT (NOG 2.6.2.1) US · FRT
- ERCOT (NOG 2.9.1.2 legacy) US · HVRT, LVRT
- ERCOT (NOG 2.9.1) US · HVRT, LVRT
- IEEE 1547-2018 Cat III US · FRT, HVRT, LVRT
- IEEE 2800-2022 US · FRT, HVRT, LVRT
- Mexico (Codigo de Red) Mexico · FRT, HVRT, LVRT
- NERC PRC-024-4 (ERCOT) US · FRT
- NERC PRC-024-4 (no-trip) US · HVRT, LVRT
- NERC PRC-024-4 (Western) US · FRT
- NERC PRC-029-1 (Table 1: AC-connected wind IBR /…) US · LVRT