Malaysia (Grid Code Additional Code 2025) — ride-through requirements
The LVRT, FRT envelopes a grid-scale battery must meet under Malaysia (Grid Code Additional Code 2025) (Malaysia), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.15s → 0 pu; 0.151s → 0.11 pu; 0.49s → 0.11 pu; 0.491s → 0.34 pu; 0.83s → 0.34 pu; 0.831s → 0.56 pu; 1.16s → 0.56 pu; 1.161s → 0.79 pu; 1.5s → 0.79 pu; 1.501s → 0.9 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 52 Hz; 3600s → 52 Hz; 3600s → 51.5 Hz; 5400s → 51.5 Hz; 5400s → 50.5 Hz | Low: 0.1s → 47 Hz; 10s → 47 Hz; 10.001s → 47.5 Hz; 5400s → 47.5 Hz; 5400s → 49.5 Hz | verified |
Where these values come from
- LVRT Grid Code for Peninsular Malaysia – Additional Code, KOD/ST/No.9/2025 (Suruhanjaya Tenaga), Connection Code CC.6.4.15.2 and Figure 6 'Power Park Modules and Energy Storage Units Fault Ride Through Requirements'; definition of Energy Storage Unit; CC.6.2.4.1.
- FRT Grid Code for Peninsular Malaysia – Additional Code, KOD/ST/No.9/2025, Connection Code CC.6.2.3.2 frequency range table.
Last checked against the source document on .
Other grid codes in Asia-Pacific
- Australia (NER / AEMO) Australia · FRT, HVRT, LVRT
- India (CEA Connectivity Regs) India · FRT, HVRT, LVRT
- New Zealand (EIPC cl 8.25A) New Zealand · HVRT
- New Zealand North Island (EIPC cl 8.19(1)) New Zealand · FRT
- New Zealand North Island (EIPC cl 8.25A) New Zealand · LVRT
- New Zealand South Island (EIPC cl 8.25A) New Zealand · LVRT
- Philippines PV (PGC 2016 Fig 4.4) Philippines · LVRT
- Philippines VRE (PGC 2016 Tables 4.1 & 4.3) Philippines · FRT
- Philippines Wind (PGC 2016 Fig 4.2) Philippines · LVRT
- Singapore (EMA Transmission Code App. F6) Singapore · FRT
- South Korea (KEPCO) South Korea · FRT, HVRT, LVRT
- Sri Lanka (CEB) Sri Lanka · FRT, LVRT