New Zealand (EIPC cl 8.25A) — ride-through requirements
The HVRT envelope a grid-scale battery must meet under New Zealand (EIPC cl 8.25A) (New Zealand), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| high-voltage ride-through (HVRT) | ride-through | 0.001s → 1.2 pu; 2s → 1.2 pu; 2.001s → 1.15 pu; 6s → 1.15 pu; 6.001s → 1.1 pu | verified |
Where these values come from
- HVRT Electricity Industry Participation Code 2010, Part 8, cl 8.25A(1) and (6), upper boundary of Figure 8.1 / Figure 8.2 — verified in the 1 May 2025 consolidation; clause unchanged at 1 July 2026.
Last checked against the source document on .
Other grid codes in Asia-Pacific
- Australia (NER / AEMO) Australia · FRT, HVRT, LVRT
- India (CEA Connectivity Regs) India · FRT, HVRT, LVRT
- Malaysia (Grid Code Additional Code 2025) Malaysia · FRT, LVRT
- New Zealand North Island (EIPC cl 8.19(1)) New Zealand · FRT
- New Zealand North Island (EIPC cl 8.25A) New Zealand · LVRT
- New Zealand South Island (EIPC cl 8.25A) New Zealand · LVRT
- Philippines PV (PGC 2016 Fig 4.4) Philippines · LVRT
- Philippines VRE (PGC 2016 Tables 4.1 & 4.3) Philippines · FRT
- Philippines Wind (PGC 2016 Fig 4.2) Philippines · LVRT
- Singapore (EMA Transmission Code App. F6) Singapore · FRT
- South Korea (KEPCO) South Korea · FRT, HVRT, LVRT
- Sri Lanka (CEB) Sri Lanka · FRT, LVRT