Sri Lanka (CEB) — ride-through requirements
The LVRT, FRT envelopes a grid-scale battery must meet under Sri Lanka (CEB) (Sri Lanka), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.14s → 0 pu; 0.141s → 0.13 pu; 0.49s → 0.13 pu; 0.491s → 0.4 pu; 0.85s → 0.4 pu; 0.851s → 0.67 pu; 1.2s → 0.67 pu; 1.201s → 0.8 pu; 2.5s → 0.8 pu; 2.501s → 0.85 pu; 180s → 0.85 pu; 180.001s → 0.9 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 53 Hz; 20s → 53 Hz; 20.001s → 52 Hz; 1200s → 52 Hz; 1200s → 51.5 Hz; 5400s → 51.5 Hz; 5400s → 51 Hz | Low: 0.1s → 47 Hz; 60s → 47 Hz; 60.001s → 47.5 Hz; 5400s → 47.5 Hz; 5400s → 49 Hz | verified |
Where these values come from
- LVRT Ceylon Electricity Board, Grid Connection Code, Grid Code - Revised September 2023 (PDF published July 2024, ceb.lk '1723552921Grid_Connection_Code_for_publishing_in_CEB_web.pdf'), section 3.17.3 'Fault Ride Through / Low Voltage Fault Ride Through (LVRT)', Figure 3.17-10 'Fault Ride Through requirement - Voltage duration curve' (p.32).
- FRT CEB Grid Connection Code, Grid Code - Revised September 2023 (published July 2024), section 3.17.1.1 'Frequency ranges' I. Operating ranges (b), table on p.20.
Last checked against the source document on .
Other grid codes in Asia-Pacific
- Australia (NER / AEMO) Australia · FRT, HVRT, LVRT
- India (CEA Connectivity Regs) India · FRT, HVRT, LVRT
- Malaysia (Grid Code Additional Code 2025) Malaysia · FRT, LVRT
- New Zealand (EIPC cl 8.25A) New Zealand · HVRT
- New Zealand North Island (EIPC cl 8.19(1)) New Zealand · FRT
- New Zealand North Island (EIPC cl 8.25A) New Zealand · LVRT
- New Zealand South Island (EIPC cl 8.25A) New Zealand · LVRT
- Philippines PV (PGC 2016 Fig 4.4) Philippines · LVRT
- Philippines VRE (PGC 2016 Tables 4.1 & 4.3) Philippines · FRT
- Philippines Wind (PGC 2016 Fig 4.2) Philippines · LVRT
- Singapore (EMA Transmission Code App. F6) Singapore · FRT
- South Korea (KEPCO) South Korea · FRT, HVRT, LVRT