Transient overvoltage (IEEE 2800 TOV) — ride-through requirements
The HVRT envelope a grid-scale battery must meet under Transient overvoltage (IEEE 2800 TOV) (US), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| high-voltage ride-through (HVRT) | ride-through | 0.0001s → 1.8 pu; 0.0002s → 1.8 pu; 0.00021s → 1.7 pu; 0.001s → 1.7 pu; 0.00101s → 1.6 pu; 0.003s → 1.6 pu; 0.00301s → 1.4 pu; 0.015s → 1.4 pu; 0.0151s → 1.2 pu | verified |
Where these values come from
- HVRT IEEE 2800-2022 Table 14 (transient overvoltage ride-through), reproduced with IEEE copyright permission on slide 48 of the official IEEE PES / IEEE 2800 WG + SEIA/ACP joint webinar: 'V > 1.80 — see footnote a (surge protection); V > 1.70 — 0.2 ms; V > 1.60 — 1.0 ms; V > 1.40 — 3.0 ms; V > 1.20 — 15.0 ms', footnote c 'specified voltage magnitudes are the residual voltages with surge arresters applied', footnote d 'cumulative time over a 1-min time window', axis label 'Voltage at RPA (per unit of nominal instantaneous peak base)'. Clause text quoted in P. Pourbeik (PEACE/Invenergy), 'Thoughts on IEEE 2800-2022 TOV Ride-Through Requirement', ERCOT IBRWG 14 Jun 2024. Independently corroborated by the ERCOT NOGRR245 capability form, whose TOV rows are footnoted '*These requirements are from IEEE 2800-2022': 1.8 pu → 0.0002 s, 1.7 → 0.001 s, 1.6 → 0.003 s, 1.4 → 0.015 s.
Last checked against the source document on .
Other grid codes in North America
- California Rule 21 US · FRT, HVRT, LVRT
- Canada (Alberta AESO) Canada · FRT, HVRT, LVRT
- ERCOT (NOG 2.6.2.1) US · FRT
- ERCOT (NOG 2.9.1.2 legacy) US · HVRT, LVRT
- ERCOT (NOG 2.9.1) US · HVRT, LVRT
- IEEE 1547-2018 Cat III US · FRT, HVRT, LVRT
- IEEE 2800-2022 US · FRT, HVRT, LVRT
- Mexico (Codigo de Red) Mexico · FRT, HVRT, LVRT
- NERC PRC-024-4 (ERCOT) US · FRT
- NERC PRC-024-4 (no-trip) US · HVRT, LVRT
- NERC PRC-024-4 (Western) US · FRT
- NERC PRC-029-1 (IBR) US · FRT, HVRT, LVRT