Austria (E-Control TOR Typ D) — ride-through requirements

The LVRT, FRT envelopes a grid-scale battery must meet under Austria (E-Control TOR Typ D) (Austria), digitized breakpoint by breakpoint and checked against the clause it came from.

Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.

What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.

Breakpoints

Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.

Event Duty Breakpoints Status
low-voltage ride-through (LVRT) ride-through 0.001s → 0 pu; 0.15s → 0 pu; 0.49s → 0.21 pu; 0.83s → 0.43 pu; 1.16s → 0.64 pu; 1.5s → 0.85 pu verified
frequency ride-through (FRT) ride-through High: 0.1s → 51.5 Hz; 1800s → 51.5 Hz; 1800s → 51 Hz | Low: 0.1s → 47.5 Hz; 3600s → 47.5 Hz; 3600s → 48.5 Hz; 9000s → 48.5 Hz; 9000s → 49 Hz verified

Where these values come from

  • LVRT E-Control, 'TOR Stromerzeugungsanlagen: Anschluss und Parallelbetrieb von Stromerzeugungsanlagen des Typs D' (Maximalkapazitat >= 50 MW oder Nennspannung >= 110 kV), Version 1.3, gultig ab 01.07.2024 - Kapitel 5.2.1, Abbildung 12 (FRT-Profil nichtsynchroner Stromerzeugungsanlagen, Anschluss auf oder oberhalb der 110-kV-Ebene), p. 28.
  • FRT E-Control, 'TOR Stromerzeugungsanlagen Typ D', Version 1.3, gultig ab 01.07.2024 - Kapitel 5.1.1 'Frequenzbereiche', Tabelle 1 (including footnote 14 on the 90-minute band).

Last checked against the source document on .