Vietnam BESS (Circular 05/2025/TT-BCT Art. 44) — ride-through requirements
The LVRT, HVRT, FRT envelopes a grid-scale battery must meet under Vietnam BESS (Circular 05/2025/TT-BCT Art. 44) (Vietnam), digitized breakpoint by breakpoint and checked against the clause it came from.
Part of: the grid-code ride-through chart — compare this against 63 other standards in 42 countries.
What this is, and is not. A reading aid compiled from the clause cited below — not a compliance document. The primary text governs. Every value here was read from a current primary source.
Breakpoints
Times are seconds from the start of the disturbance. Voltage is per-unit of nominal; frequency in hertz. An LVRT curve is a lower boundary (stay connected while voltage is on or above it), an HVRT curve an upper boundary, and FRT gives the band between its High and Low boundaries.
| Event | Duty | Breakpoints | Status |
|---|---|---|---|
| low-voltage ride-through (LVRT) | ride-through | 0.001s → 0 pu; 0.15s → 0 pu; 0.151s → 0.3 pu; 0.6s → 0.3 pu; 0.601s → 0.38 pu; 1.2s → 0.38 pu; 1.201s → 0.53 pu; 1.8s → 0.53 pu; 1.801s → 0.68 pu; 2.4s → 0.68 pu; 2.401s → 0.83 pu; 3s → 0.83 pu; 3.001s → 0.9 pu | verified |
| high-voltage ride-through (HVRT) | ride-through | 0.001s → 1.2 pu; 0.5s → 1.2 pu; 0.501s → 1.15 pu; 3s → 1.15 pu; 3.001s → 1.1 pu | verified |
| frequency ride-through (FRT) | ride-through | High: 0.1s → 52 Hz; 60s → 52 Hz; 60.001s → 51.5 Hz; 1800s → 51.5 Hz; 1800s → 51 Hz | Low: 0.1s → 47.5 Hz; 600s → 47.5 Hz; 600.001s → 48 Hz; 1800s → 48 Hz; 1800s → 49 Hz | verified |
Where these values come from
- LVRT Circular 05/2025/TT-BCT dated 1 February 2025, Article 44 clause 3(a)-(c), as consolidated with Circular 46/2025/TT-BCT (in force 22 September 2025); identical envelope at Article 40 clause 6.
- HVRT Circular 05/2025/TT-BCT dated 1 February 2025, Article 44 clause 3(c), 3(d) and 3(đ), as consolidated with Circular 46/2025/TT-BCT; identical envelope at Article 40 clause 6.
- FRT Circular 05/2025/TT-BCT dated 1 February 2025, Article 44 clause 1, Table 17, as consolidated with Circular 46/2025/TT-BCT; identical table at Article 40 clause 2, Table 11.
Last checked against the source document on .
Other grid codes in Asia-Pacific
- Australia (NER / AEMO) Australia · FRT, HVRT, LVRT
- India (CEA Connectivity Regs) India · FRT, HVRT, LVRT
- Malaysia (Grid Code Additional Code 2025) Malaysia · FRT, LVRT
- New Zealand (EIPC cl 8.25A) New Zealand · HVRT
- New Zealand North Island (EIPC cl 8.19(1)) New Zealand · FRT
- New Zealand North Island (EIPC cl 8.25A) New Zealand · LVRT
- New Zealand South Island (EIPC cl 8.25A) New Zealand · LVRT
- Philippines PV (PGC 2016 Fig 4.4) Philippines · LVRT
- Philippines VRE (PGC 2016 Tables 4.1 & 4.3) Philippines · FRT
- Philippines Wind (PGC 2016 Fig 4.2) Philippines · LVRT
- Singapore (EMA Transmission Code App. F6) Singapore · FRT
- South Korea (KEPCO) South Korea · FRT, HVRT, LVRT